Inxpect C201A FSoE Control Unit

C201 is the most advanced control unit for Inxpect safety radars, with the widest range of communication options. The Inxpect Safety Application allows the configuration of sensitive levels, safety functions, size detection fields, and the functionality of the I/O ports of the control unit.
Safety fieldbus: Currently supporting Safety over EtharCAT® (FSoE) fieldbus protocol.
Secure Ethernet: Remote configuration and management protected by industry standard cyber security protocols.
USB: Local configuration option.
Digital inputs: The system has two TYPE3 dual channel inputs. Alternatively, the four channels can be used as single channel digital inputs (category 2). Supporting the following functions:
  • Muting signal
  • Emergency stop signal
  • restart signal

Four Output Sinal Switching Devices:

  • As safety outputs: two dual-channel safety OSSDs
  • As auxiliary output: four auxiliary outputs, which can be configured as signal restart feedback, fault, muting status.

Dynamic setting of detection fields: The FSoE connection allows to have up to 32 configurations switchable in real time.

Type A:

  • C201A-F (Core line) Part no. 90301012
  • C201A-FX1 (eXtended line) Part no. 90301012.2BO

The eXtended Line supports new advanced functions. It also supports S202A sensors and Inxpect Safety Studio application.

Categories: ,

Description

  • FSoE and MODBUS
  • Outputs: 4 Outputs Signal Switching Devices (OSSDs) or 2 dual channel safety outputs
  • Safety outputs: High-side outputs (with extended protection function) Max voltage: 30 V dc | Max current: 0.4 A | Max power: 12 W
  • Inputs: 2 dual channel TYPE3 digital inputs with common GND, 4 single channel TYPE3 digital inputs with common GND
  • Fieldbus interface: Ethernet based safety fieldbus (Safety over EtherCAT® FSoE)
  • MODBUS interface: Ethernet interface for real time data monitoring
  • Power supply: 24 V dc (20–28 V dc) Max current: 1 A (no OSSD)
  • Max power consumption: 5 W (no OSSD)
  • Assembly: DIN guide
  • Degree of protection: IP20
  • Terminals: Section: 1mm2 | Max Current: 4 A with 1mm2 cables
  • System configuration: Ethernet, USB

 

Go to Top